After a visual inspection the very next step for the most seasoned technicians is pulling out their gauges and checking the pressure and temperature. It just becomes second nature after enough calls.

Andrax tutorial

It will never fail that one of the first questions the pros ask the rookie is what is your subcool and what is your superheat? This article aims at providing you with just that information. There had to be a replacement for the Ozone damaging refrigerants of the past and the successor was the HFC RA that we all know of today. RA has one of the highest Global Warming Potential numbers of any modern day refrigerant and is known as a super pollutant.

Because of this we are seeing various countries and manufacturers no longer using RA in new machinery. Instead, companies and countries are opting for more climate friendly refrigerants such as natural refrigerants, hydrocarbons, and newer less GWP heavy HFO refrigerants.

There you have it folks. I hope this article was helpful and if you find that something is inaccurate here in my chart please do not hesitate to reach out to me. I have sourced this the best I could but there is always going to be conflicting data. The aim with this article is to give you accurate information so again, if you see anything incorrect please let me know by contacting me here.

RefrigerantHQ's Pressure Charts. You may also like. We do not directly sell any products or refrigerants, but rather provide information, knowledge, and explanations to the consumer. This content is provided 'As is' and is subject to change or removal at any time.

freezer 404a pressure

Privacy Privacy Policy Disclaimer Advertising.If we can't tunnel through the Earth, how do we know what's at its center? What should the high and low pressures be for A refrigerant on a freezer? A lady introduce her husband's name with saying by which can stop or move train what is that name. Give points yo advocate thst biology is linked with physics chemistry mathsmatics geography. All Rights Reserved. The material on this site can not be reproduced, distributed, transmitted, cached or otherwise used, except with prior written permission of Multiply.

Hottest Questions. Previously Viewed. Unanswered Questions. Home Appliances. Mechanical Engineering. Wiki User I got it ,but the mention pressure of suction discharge at what temprature in centegrade it should be. Related Questions Asked in Thunderstorms and Lightning What should the high and low pressures be for A refrigerant on a walk in cooler? Asked in Refrigerators What is the property of refrigerant A? No, refrigerants cannot be blended.

Asked in Refrigerators What type of refrigerant do you need in a high temp walk in freezer? Newer freezers compliant to efficiency standards use Ra.

Fat free framework plugins

However an older unit may only be able to us R which will be completely phased out by Asked in Definitions Define a near-azeotropic refrigerant blend and give two examples? Asked in Science Could ra mix with r? Ra is a substitute for r refrigerant but requires the system to be charged with POE lubricant. R is being phased out by international protocols.Listed below are field service terms or trade jargon often used to describe these pressures.

Condensing pressure: High-side pressure, head pressure, discharge pressure.

Normal Range of Operating Pressures for 404A?

Evaporating pressure: Low-side pressure, suction pressure, back pressure. Figure 1.

R404a Gas charging - -40° machine me kaise karte hai - -40°c - DhuriyaJi Tech News

A basic refrigeration system showing refrigerant pressures, states, and conditions. Condensing Pressure The condensing pressure is the pressure at which the refrigerant is phase changing from a vapor to a liquid. This phase change is referred to as condensation. Thus the term condensing pressure. This pressure can be read directly from a pressure gauge connected anywhere between the compressor's discharge valve and the entrance to the metering device, assuming that there is negligible pressure drop.

In reality, line and valve friction and the weight of the liquid itself cause pressure drops from the discharge of the compressor to the metering device. If a true condensing pressure is needed, the technician must measure the pressure as close to the condenser as possible to avoid these pressure drops. This pressure is usually measured on smaller systems near the compressor's valves.

On these small systems, it is not critical where a technician places the pressure gauge as long as it is on the high side of the system because pressure drops are negligible.

The pressure gauge will read the same no matter where it is on the high side of the system if line and valve losses are negligible. Evaporating Pressure The evaporating pressure is the pressure at which the refrigerant is phase changing from a liquid to a vapor. This phase change is referred to as evaporation or vaporizing, thus the term evaporating pressure. A pressure gauge placed anywhere between the metering device outlet and the compressor will read the evaporating pressure.

Again, negligible pressure drops are assumed. In reality, there will be line and valve pressure drops as the refrigerant travels through the evaporator and suction line. So, the technician must measure the pressure as close to the evaporator as possible to get a true evaporating pressure.

On small systems where pressure drops are negligible, this pressure is usually measured near the compressor. Again, on small systems, gauge placement is not critical as long as it is placed on the low side of the refrigeration system.The ubiquitous walk-in cooler or freezer is an essential part of many cafeterias, restaurants and convenience stores.

Ladki ko ignore kaise kare

It is also a large energy user in these facilities but is rarely considered until problems emerge. Problems include failure to maintain pressure and compressor failure, both of which can result in expensive losses to the products stored in the cooler.

These problems, as well as unnecessarily high energy use, can be avoided by observing equipment and taking corrective action. Evaporators Moisture from the air freezes onto the evaporator coils the cooling coils in the freezer and forms an insulating barrier to heat transfer. Airflow also decreases as the passages narrow due to ice buildup. Water from the melted ice is drained from the freezer. When the coil freezes, heat transfer is greatly reduced resulting in the compressor working harder and longer.

It works harder because the suction pressure drops making the compressor work at a higher differential pressure, thus requiring more power. It works longer because heat transfer is reduced. When ice buildup is excessive, the compressor will run all the time and the freezer temperature setpoint will not be maintained.

As the ice melts, the water has to drain out of the freezer. Trapped water that freezes can do significant structural damage to a freezer; especially older ones where cracks allow water to seep in, then freeze and expand. Stalactites and stalagmites of ice appearing in your freezer are reason for swift action to avoid costly damage. Condensers The condenser coil of the refrigeration system removes heat from the system. The temperature around the compressor rises resulting in higher head pressure for the compressor, which again increases compressor power.

To effectively remove heat, the condenser should be placed in a well-ventilated area where the temperature is controlled to allow heat to be removed easily. Enclosed spaces will require openings for cooling air intake and exhaust. In many cases, a fan will be required to move enough air through the space. If the condenser heat is never needed, it should be exhausted directly outside if possible.

In cases where it may be used for space heating — such as for a nearby dry storage room — controls may be installed to direct the flow indoors for heating, and outdoors when heating is not required. Condenser coils should also be checked regularly for cleanliness.

Dust and debris will act like ice buildup on an evaporator coil. This will insulate the heat transfer surface and reduce airflow, which will make the compressor run harder and longer. In extreme cases, compressors may fail. The shell of the cooler or freezer should be inspected regularly for leaks and loose insulation or panels.

Leaks and other voids in the shell can cause excess moisture to accumulate, potentially causing even bigger problems.

walk-in freezer with super high super heat

The door is also a key component of the cooler. Doors must be sealed properly to eliminate air infiltration which increases the cooling load and may cause moisture buildup within the space and on the evaporator. Frost buildup on the door itself is a common occurrence when the door heater fails and has a tendency to either freeze the door shut or keep it from closing. Proper care should also be taken when placing items inside the space.Remember Me? Page 1 of 5 1 2 3 4 5 Last Jump to page: Results 1 to 13 of Thread: RA Freezer.

First time using and installing a freezer split system with A. Can some one tell me LP,HP settings. Box is using a LL Soleniod for pump down operation with stat. System is air cooled walk in box. What would be normal operating pressure and super heat?? Hp safety out. Look for B. VTP99 liked this post. Pressures similar tohead may be a little higher under load or in hot weather. Normal head would be depending on outside temp and load conditions. Suction depending on inside temp. LP-cut out around 5 psi, don't pull into a vacuum.

freezer 404a pressure

Make sure the condenser can breath. Good luck. Note concerning the difference in my and Mo's reccomended HP setting. Depends in part where you are. Here in the hot south you'll nusience trip unless you set it high. Up north you can get by with a lower setting. Not fast enough there K! And I'll be ripping out some Beacon goodies not my choice for sure.

Head Pressure Rec mmending psig for high pressure cutout is pushing! This is kind of pushing into the danger zone is it not!?Forums Forum list Search forums. What's new New posts New profile posts Latest activity.

Members Current visitors New profile posts Search profile posts. Log in Register. Search titles only. Search Advanced search…. Forum list. Search forums. Log in. We have a lot of fun, but make no mistake, we are pros. Hvacproforums is self supporting Do-it-yourselfers and Homeowners are encouraged to seek information elsewhere. Those involved in the HVAC industry are urged to register.

Slow Site? JavaScript is disabled. For a better experience, please enable JavaScript in your browser before proceeding.

Status Not open for further replies. Are your gauges reading the correct pressures? Is the sight glass clear and what is your subcool? HMD Half-Ass.

freezer 404a pressure

I have triple checked. Ah that's better. Whats the subcool then?

Viper ds4vb installation manual

So your liquid line is degs. Thats an awful hot condenser. Keep looking for your restriction and sign in please! Have a cold one and stand back for a while. Tomorrow is another day.

R-404A Refrigerant Pressure Temperature Chart

You work for yourself or a company? The txv should be adjustable, open it up. I work 7days and all holidays.I've read so much different BS on how to charge a liquid a into a system its ridiculous and now I'm starting to get confused.

I really wish if people didn't know wtf they were talking about they wouldn't input or give advice on the procedure. So, I typically input the a as a liquid on the high pressure side at the king valve coming out of the receiver WITH the system running. Is this the correct method? I hear people say leave the system running, shut it off, throttle the in the low pressure vapor side as a liquid, etc. What is the real procedure and BEST procedure when charging in a liquid state?

And when would you ever want to charge the A on the low pressure side if ever? What you are doing is fine, but it is only one of the ways to do it.

It is not BS realy it is common sense. Put the refrigerant in the system anyway you want just do it in liquid form. It does not matter. It honestly doesn't What does matter is that you are comfortable doing it the way you do.

I heard though that when charging via liquid on the suction side it could and would damage the compressor? As liquids don't compress and BOOM there goes your compressor. So is the proper procedure to throttle it in while the system is running or while its off if doing it near the compressor on the suction side?

I would charge enough liquid to run the system into the reciever with the system off, then run it up and charge into the suction valve on the compressor, i would throttle the valve on the gauge manifold so that little or no liquid reached the suction valve on the compressor.

Effectivly turning the gauges into a hand expansion valve. If you are not charging the whole bottle, so long as the refrigerant leaves the bottle as a liquid, it doesn't matter if it vapourises before reaching the system.

And as Cool runnings says if you are putting the whole bottle into the one system you can charge as a vapour. High side charging with the system running is not how you do it. You could pump your can full and explode it. Dumping liquid into to high side is a normal practice with the system off. As is metering liquid into the low side when it's running.